The D2xC1X05 features a high output, 116dB(A) alarm horn sounder (measured at 1 meter) combined with a 5 Joule Xenon strobe warning light / beacon. Globally approved, the robust Type 4/4X, IP66 enclosure ensures suitability for all haz loc fire alarm and general signaling applications. The corrosion proof, marine grade aluminum die cast enclosure is chromated and powder coated providing resilience in the harshest of hazardous location environments. One device, globally certified: ATEX, IECEx Zone 2 & 22; NEC/CEC CI D2 and CII D2; NEC CI Zone 2 and Zone 22; CEC Zone 2 & 22 and CII D2. UL & cUL approved 24Vdc version for fire alarm use.

We have listed this model with the most common options/configurations, other specific configurations are available--see Catalog Page link below and inquire. This version allows for selection of the Housing color, the voltage option, and the lens color option. This version is preconfigured for:

  • Entries: 2 × 3/4"NPT – adaptors (option "C")
  • Stopping Plugs: Nickel Plated (option "N")
  • Guard material: A4 316 Stainless Steel (option "1")
  • Product Version: UL, cUL, IECEx, ATEX, CSFM, Ex EAC (option "A")
  • Product Option: Standard Product (option "1")


Features:
  • 5 Joule Xenon beacon with 116dB(A) alarm horn (measured at 1 meter)
  • UL464/UL1638 Fire Alarm
  • Effective Intensity: 94.78 cd Peak Candela: 33,410 cd
  • 64 alarm tones, 4 remotely selectable alarm stages/channels
  • Field replaceable lens color filters
  • Dual cable entries Supplied with haz loc rated stopping plugs/adaptors

Approvals:
  • UL File ref: E230764
  • IECEx cert: IECEx ULD 14.0004X
  • ATEX cert: EMKO 14 ATEX 4786493904X
  • CSFM listing: 7136-2279:0503
  • Ex EAC certified: EAC RU C GB.AA71.B.00273/20

Coding NEC / CEC:
  • Class I Div 2 ABCD T2B Ta -40°C to +70°C
  • Class I Div 2 ABCD T2C Ta -40°C to +55°C
  • Class I Div 2 ABCD T2D Ta -40°C to +40°C
  • Class II Div 2 FG T5 Ta -40°C to +50°C
  • Class III Div 1&2 Ta -40°C to +50°C

Voltages Available:
  • Voltage DC: 24V dc (UL/cUL Fire Alarm)
  • Voltage AC: 115Vac (110-120Vac), 230Vac (220-240Vac)

Specification:
Alarm Horn Sounder: 
  • Maximum output: 116dB(A) @ 1 metre [107dB(A) @ 10ft/3m]
  • Nominal output: 112dB(A) @ 1m +/- 3dB – Tone 2 [103dB(A) @ 10ft/3m]
  • No. of tones: 64 (UKOOA / PFEER compliant)
  • No. of stages: 4 
  • Volume control: Adjustable -12dB(A) [Tone 2]
  • Effective range: 125m/410ft @ 1KHz
  • Stage switching: DC units – Positive or Negative line. AC units – common supply line

Xenon Strobe Beacon:
  • Beacon: Energy: 5 Joules (5Ws)
  • Flash rate: 1Hz (60 fpm)
  • Peak Candela: 500,000 cd – calculated from energy (J)
  • Effective Intensity cd: 250 cd – calculated from energy (J)
  • Peak Candela: 33,410 cd – measured ref. to I.E.S.
  • Effective Intensity: 94.78 cd – measured ref. to I.E.S.
  • Lens colors: Amber, Blue, Clear, Green, Magenta, Red 
  • Tube life: Emissions are reduced to 70% after 8 million flashes

General:
  • Voltages DC: 24V dc [20-28Vdc]; 48V dc [38-58Vdc]
  • In rush: 2.2A for <9ms Voltages AC: 115V ac 50/60Hz; 230V ac 50/60Hz 
  • Ingress protection: EN60529: IP66 UL50E / NEMA250: 4 / 4X / 3R / 13
  • Enclosure material: Marine grade aluminum LM6